Rear Against Wall Temperature rise (Kelvin)
Dissipation

APO 1
185x150x130

APO 31
300x185x175

APO 41
300x300x175

APO 71
370x300x175

APO 51
485x300x175

APO 81
555x300x175

APO 61
600x300x175

APO 11
600x370x175
APO 12
600x600x175
Watt Half Top Half Top Half Top Half Top Half Top Half Top Half Top Half Top Half Top
5 12 14 7 9 6 7 5 6 4 5 4 5 4 5 3 4 3 3
10 20 25 12 15 10 12 9 11 8 9 7 9 7 8 6 7 4 5
15 28 34 17 21 14 16 12 15 10 13 10 12 9 11 8 10 6 7
20 36 43 22 27 17 20 15 19 13 16 12 15 11 14 10 13 8 9
25 43 52 26 32 21 24 18 22 16 19 14 18 14 17 12 15 9 11
30 30 37 24 28 21 26 18 22 17 21 16 20 14 17 11 13
40 38 47 30 36 27 32 23 28 21 26 20 25 18 22 14 16
50 45 56 36 43 32 39 27 34 25 31 24 30 21 26 16 19
60 42 49 37 45 32 39 29 36 28 34 25 30 19 22
70 42 51 36 44 33 41 31 39 28 34 21 25
80 40 49 37 46 35 43 31 38 24 28
90 40 50 38 48 34 42 26 31
100 42 52 37 46 28 34
110 40 50 31 36
120 43 53 33 39
130 35 42
140 37 44
150 39 47
160 41 49
170 45 53

Front, left and upperside free Temperature rise (Kelvin)
Dissipation APO 1 185x150x130

APO 31
300x185x175

APO 41
300x300x175

APO 71
370x300x175

APO 51
485x300x175

APO 81
555x300x175

APO 61
600x300x175

APO 11
600x370x175
APO 12
600x600x175
Watt Half Top Half Top Half Top Half Top Half Top Half Top Half Top Half Top Half Top
5 13 15 8 9 6 7 5 6 5 6 4 5 4 5 4 4 3 3
10 22 27 13 16 11 13 9 11 8 10 7 9 7 9 6 8 5 5
15 30 37 18 23 15 18 13 15 11 14 10 13 10 12 9 11 6 8
20 38 46 23 28 19 22 16 19 14 17 13 16 12 15 11 13 8 10
25 46 56 28 34 22 27 19 23 17 21 15 19 15 18 13 16 10 11
30 32 39 26 31 22 27 19 24 18 22 17 21 15 19 11 13
40 40 50 33 39 28 34 24 30 22 28 19 24 19 23 14 17
50 39 46 33 41 29 36 27 33 25 32 23 28 17 20
60 45 54 39 47 34 42 31 39 29 37 26 32 19 23
70 44 53 38 47 35 44 33 42 30 37 22 26
80 42 52 39 49 37 46 33 41 25 29
90 43 53 41 51 36 45 27 32
100 39 49 29 35
110 43 53 32 38
120 34 40
130 36 43
140 39 46
150 41 48
160 43 51
170

Frontside and upperside free Temperature rise (Kelvin)
Dissipation APO 1 185x150x130

APO 31
300x185x175

APO 41
300x300x175

APO 71
370x300x175

APO 51
485x300x175

APO 81
555x300x175

APO 61
600x300x175

APO 11
600x370x175
APO 12
600x600x175
Watt Half Top Half Top Half Top Half Top Half Top Half Top Half Top Half Top Half Top
5 13 16 8 10 7 8 6 7 5 6 5 6 4 5 4 5 3 3
10 24 29 14 18 11 14 10 12 8 10 8 10 7 9 7 8 5 6
15 33 40 20 24 16 19 14 17 12 15 11 14 10 13 9 11 7 8
20 41 50 25 31 20 24 17 21 15 18 14 17 13 16 12 14 8 10
25 30 37 24 28 21 25 18 22 16 20 16 20 14 17 10 12
30 34 42 28 33 24 29 20 25 19 24 18 23 16 20 12 14
40 43 54 35 41 30 37 26 32 24 30 23 29 20 25 15 17
50 42 49 36 44 31 38 29 36 27 34 24 30 17 21
60 48 57 42 51 36 44 33 41 32 39 28 35 20 24
70 40 50 38 47 36 45 32 39 23 27
80 42 52 40 50 35 44 26 30
90 39 48 28 33
100 42 52 31 36
110 33 39
120 35 42
130 38 45
140 40 48
150 42 50
160
170

Frontside free, upperside not free Temperature rise (Kelvin)
Dissipation APO 1 185x150x130

APO 31
300x185x175

APO 41
300x300x175

APO 71
370x300x175

APO 51
485x300x175

APO 81
555x300x175

APO 61
600x300x175

APO 11
600x370x175
APO 12
600x600x175
Watt Half Top Half Top Half Top Half Top Half Top Half Top Half Top Half Top Half Top
5 15 18 9 11 7 8 6 8 5 6 5 6 5 6 4 5 3 4
10 25 31 16 19 12 15 11 14 9 11 8 10 8 10 7 9 5 6
15 35 43 22 27 17 21 16 19 13 16 12 14 11 14 10 12 7 9
20 44 54 27 34 22 26 20 24 16 20 15 18 14 17 12 15 9 11
25 33 41 26 31 23 29 19 23 18 22 17 21 15 18 11 13
30 38 47 30 36 27 33 22 27 20 25 19 24 17 21 13 15
40 48 59 38 45 34 42 28 34 26 32 24 30 22 27 16 19
50 46 54 41 50 33 41 31 38 29 36 26 32 19 22
60 38 47 35 44 34 42 30 37 22 26
70 43 54 40 50 38 48 34 42 25 29
80 43 53 38 47 28 33
90 42 51 30 36
100 33 39
110 36 42
120 38 45
130 41 48
140 43 51
150
160
170