Integrated with Contactor, Standard Interuption Capacity

GE Controls, North American Catalog, IEC Manual Motor Starters

45 mm Standard Interruption Capacity (Toggle Operator)
Integrated with Mini Contactor

45 mm Standard Interruption Capacity (Toggle Operator) Integrated with Mini Contactor

Open, AC Operated Contactors

Standard Interruption Capacity

Individual or Group Installation Manual Starter Type GPS1BS

Selection of the starter depends on the actual motor full load current and service factor. For motors with service factor of 1.15 or greater, use motor full load current to select the appropriate current range. For motors with a service factor less than 1.15, multiply the normal full load current by .9 for the current setting. Single phase applications require all three overload legs to be energized for proper operation. Use separate conductor to connect terminal T2 to L3. Connect power to L1 and L2 and apply load between T1 and T3.

45 mm Standard Interruption Capacity (Toggle Operator)
Integrated with Mini Contactor

45 mm Standard Interruption Capacity (Toggle Operator) Integrated with Mini Contactor

Open, DC Operated Contactors

Standard Interruption Capacity

Individual or Group Installation Manual Motor Starter Type GPS1BH